42
M5LCX-2009
There must be a double pole switch with
a minimum 3mm contact gap and fuse/
circuit breaker as recomended in the xed
installation circuit.
!
Wiring
Important: The gures shown in the table are for information purpose only. They should be checked and
selected to comply with the local/national codes of regulations. This is also subject to the type of installation
and conductors used.
Model M5LCX010/015C/CR M5LCX020/025C/CR
Voltage range 220V-240V / 1 Ph / 50Hz +
Power supply cable size (mm
2
) 1.5 2.5
Number of wire 3 3
Interconnection cable size (mm
2
) 1.5 2.5
Number of wire 3 3
Recommended time delay fuse (A) 15 20
• All wires must be rmly connected
• All wires must not touch the refrigerant piping, compressor or any moving parts of the fan motor.
• The connecting wires between the indoor unit and the outdoor unit must be clamped on the wire clamps as
shown in the gure.
• The power supply cord must be equivalent to H05RN-F (245IEC57) which is the minimum requirement.