126
3
rd
Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 37°C DB
Total capacity, TC
Interpolation Method:
⇒
⇒ x = 2.450kW
Sensible capacity, SC
Interpolation Method:
⇒
⇒ y = 1.774kW
40°C - 35°C
=
2.335kW - 2.526kW
40°C - 37°C 2.335kW - x
40°C - 35°C
=
1.654kW - 1.854kW
40°C - 37°C 1.654kW - y
Outdoor DB ° C
Indoor DB Indoor WB 35 37 40
° C ° C TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)
23 15 2.526 1.854 xy2.335 1.654