Filtration (Standard) – Room side return air shall be completely ltered through a permanent, washable
polypropylene mesh lter. Foam type lters are not acceptable. Filter must be a UL listed class II, 38% average
arrestance efciency (ASHRAE test) air lter with low resistance to airow (0.02 w.g. at 300 CFM) and high dust
holding capacity of 55 grams.
Wall Sleeve (Standard) (BWS) –
The BWS wall sleeve is constructed from galvanized, primed and pre-painted Antique Ivory 18 gauge steel is
insulated and arrives in a removable plastic protective lm.
Wall Sleeve (Optional) (CWS) – The CWS wall sleeve shall be entirely constructed of G-60 galvanized,
phosphatized, 18-gauge steel. It shall be nished with a baked on, epoxy based powder coat paint, which is to provide
maximum corrosion protection. Additionally, the top interior and side interior surfaces shall be insulated. Wall sleeves
with ordinary enamel nish or those made from polymeric material are not acceptable. Wall sleeves shall have factory
provisions for use of appropriate fastening devices to secure sleeve to the wall through the sides.
Outside air louvers – Shall be (stamped) (architectural) anodized aluminum as shown on plans. Louver shall be
(nished natural) (painted) as shown on the schedule. (Stamped louvers shall be heavy gauge anodized aluminum of
no less than 16-gauge). (Architectural louvers shall have rounded corners or be supplied with end caps). Special eld
fabricated louvers must be approved by the PTAC manufacturer as to free area and air circulation requirements.
Subbase (electrical) – An (3")(4") electrical subbase shall be furnished as shown on plans. Each electrical
subbase shall be UL listed and conform to the National Electrical Code. Subbase must have adjustable side channels
with predrilled adjusting holes and score lines. Subbase shall have four (4) adjustable leveling legs each with 1"
adjustment.
Subbase (hydronic) – An 8" high, hydronic heating subbase shall be furnished as shown on plans. Subbase shall
contain a 2-row, 5/8" diameter copper tubed, aluminum plate nned coil for use with hot water or steam; (normally
open) (normally closed), low voltage electric valve for (hot water) (steam) heating; and provisions for mounting a
receptacle. (Subbase must be supplied with factory installed fuse and disconnect sized for PTAC unit ampacity rating.)
The subbase must have adjustable side channels capable of extending to any wall thickness. The subbase shall have
six (6) adjustable leveling legs each with 1" adjustment.
Warranty
All McQuay equipment is sold pursuant to its standard terms and conditions of sale, including Limited
Product Warranty. Consult your local McQuay Representative for warranty details. Refer to Form
933-43285Y. To find your local McQuay Representative, go to www.mcquay.com.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.mcquay.com.
Products Manufactured in an ISO Certified Facility.
© 2009 McQuay International • www.mcquay.com • (800) 432-1342 Catalog 1300-2 (10/09)
Seitenansicht 41
1 2 ... 37 38 39 40 41 42

Kommentare zu diesen Handbüchern

Keine Kommentare