Vacuuming And Charging Method
Purging the piping and the indoor unit
The outdoor unit is equipped by two 3-way refrigerating connecting valves. The suction valve is the larger one
whereas the smaller one is the liquid valve. Both valves are supplied with service port valve for connection to a
manometer.
ó Remove the caps from the valve and the service port.
ó Connect the center manifold gauge to the vacuum pump.
ó Connect the manifold gauge to the service port of the 3-way valve.
ó Start the vacuum pump. Evacuate for approximately one hour (evacuation time varies with pump capacity).
Confi rm that the manifold gauge needle has moved towards –30inHg (-76cmHg).
ó Close the manifold valve and stop the vacuum pump.
ó On the outdoor unit, open the suction valve and
ó liquid valve (in anti-clockwise direction) with 4mm key for hexagon sacked screw.
ó The air conditioner unit is now ready for start.
ó Start the unit and run it for 10 to 15 minutes. The low pressure valve reading must be within the recommended
value range as shown in the table.
ó If the reading is within the indicated value range, the unit is running in good condition.
ó If the reading is beyond the indicated value range, the refrigerant circuit has a leak. Check and seal the leak. Top
up the charge if necessary.
ó If the reading is close to the value 0, the refrigerant circuit must be evacuated (by using vacuum pump) and be
charged (with R22) again.
MODEL
Indoor 27 °C /Outdoor 35 °C
kgf/cm2 Psi (=lbf/in2)
10 4.5 ~ 5.4 64.0 ~ 76.8
15 4.5 ~ 5.4 64.0 ~ 76.8
20 4.5 ~ 5.6 64.0 ~ 79.6
30 4.9 ~ 5.3 69.7 ~ 75.4
50 4.9 ~ 5.6 69.7 ~ 79.6
ó Within the value ó refrigerant cycle normal.
ó Lower than the value ó refrigerant cycle leaks. Check, repair and top-up.
ó Too low ( ̃ zero) ó need evacuation and charge
GAS VALVE
REFRIGERANT PIPING
VACUUM PUM
P
OUTDOOR UNIT
LIQUID VALVE
MANIFOLD
LOW SIDE
PRESSURE GAUGE
PRESSURE GAUGE
HIGH SIDE
FLEXIBLE HOSE
INDOOR UNIT