Page 41
TUBE D A (mm)
Inch mm Imperial Rigid
1/4” 6.35 1.3 0.7
3/8” 9.52 1.6 1.0
1/2” 12.70 1.9 1.3
5/8” 15.88 2.2 1.7
3/4” 19.05 2.5 2.0
Piping Work & Flaring Technique
Piping Connection To The Units
ó Align the center of the piping and tighten the fl are nut suffi ciently with fi ngers.
ó Finally, tighten the fl are nut with the torque wrench until the wrench clicks.
ó When tightening the fl are nut with the torque wrench, ensure that the tightening direction follows the arrow
indicated on the wrench.
PIPE SIZE mm (in) Torque (mm)
6.35 (1/4) 18
9.52 (3/8) 42
12.7 (1/2) 55
15.88 (5/8) 65
19.05 (3/4) 78