Page 32
Installation of MCM unit
Preliminary site survey
ó Electrical supply and installation shall conform to the local authority (e.g. National Electrical Board).
ó Voltage supply fl uctuation must not exceed ± 10% of the rated voltage. Electricity supply lines must be independent
of welding transformers which can cause high supply fl uctuation.
ó Ensure that the installation location is convenient for wiring and piping.
Standard Mounting
Ensure that the overhead supports are strong enough to hold the weight of the unit. Position the hanger rods (wall
mounting bracket for fl oor standing) and check for its alignment with the unit as shown in Figure A. Also, check that
the hangers are secured and the base of fan coil unit is leveled in both horizontal directions, taking into account the
gradient for drainage fl ow as recommended in Figure A.
Note: Dimension in mm
D
B
K
F
G
E
M
N
L
P
Q
P
O
H
A
C
I J
FIGURE A
MODEL MCM020D MCM030D MCM050D
A12141214 1714
B 666 666 666
C 273 273 273
D130130130
E11601160 1560
F272727
G777777
H 745 745 1235
I252525
J209209331
K486486486
L 108 108 108
M 360 360 600
N7707701270
O 136 136 136
P 373 373 373
Q 222 222 310