Engineering & Physical Data MVCU-2009
General Data - Cooling Only (R22)
MODEL
INDOOR UNIT MCM050D MCM062C
OUTDOOR UNIT MVCU050A MVCU060A
NOMINAL CAPACITY
Btu/h 49000 58000
W 14361 16999
NOMINAL TOTAL INPUT POWER W 4285 5141
NOMINAL RUNNING CURRENT A 8.2 8.8
POWER SOURCE V/Ph/Hz 380 - 415 / 3 / 50 380 - 415 / 3 / 50
EER W/W 3.35 3.31
REFRIGERANT TYPE R22 R22
REFRIGERANT CONTROL (EXPANSION DEVICE) INDOOR CAP. TUBE INDOOR CAP. TUBE
INDOOR UNIT
CONTROL
AIR DISCHARGE
AUTO LOUVER (UP & DOWN)
& MANUAL LOUVER (BOTTOM)
MANUAL LOUVER
OPERATION
WIRELESS OR WIRED
MICROCOMPUTER
REMOTE CONTROL
WIRELESS OR WIRED
MICROCOMPUTER
REMOTE CONTROL
AIR FLOW
HIGH l/s / CFM 491 / 1040 731 / 1550
MEDIUM l/s / CFM 448 / 950 623 / 1320
LOW l/s / CFM 387 / 820 472 / 1000
EXTERNAL STATIC PRESSURE (H/M/L) Pa / in.wg. --
SOUND PRESSURE LEVEL (H/M/L) dBA 54 / 53 / 52 56 / 53 / 46
UNIT DIMENSION
HEIGHT mm/in 249 / 9.8 285 / 11.2
WIDTH mm/in 1714 / 67.4 1903 / 74.9
DEPTH mm/in 670 / 26.3 680 / 26.8
PACKING DIMENSION
HEIGHT mm/in 345 / 13.6 368 / 14.5
WIDTH mm/in 1816 / 71.4 1984 / 78.1
DEPTH mm/in 760 / 29.9 760 / 29.9
UNIT WEIGHT kg/lb 70 / 154 85 / 187
CONDENSATE DRAIN SIZE
mm/in
19 / 3/4 19 / 3/4
OUTDOOR UNIT
AIR FLOW l/s / CFM 1944 / 4120 1944 / 4120
SOUND PRESSURE LEVEL dBA 61 63
UNIT DIMENSION
HEIGHT mm/in 1086 / 42.8 1086 / 42.8
WIDTH mm/in 762 / 30.0 762 / 30.0
DEPTH mm/in 762 / 30.0 762 / 30.0
PACKING DIMENSION
HEIGHT
mm/in
1190 / 46.9 1190 / 46.9
WIDTH mm/in 860 / 33.9 860 / 33.9
DEPTH mm/in 860 / 33.9 860 / 33.9
UNIT WEIGHT kg/lb 100 / 220 102 / 225
PIPE CONNECTION
TYPE BRAZED VALVE BRAZED VALVE
SIZE
LIQUID mm/in 9.5 / 3/8 12.7 / 1/2
GAS mm/in 19 / 3/4 19 / 3/4
REFRIGERANT CHARGE kg/lb 3.4 / 7.5 3.7 / 8.1
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT.
07_General data.indd 3507_General data.indd 35 4/28/2009 11:20:46 AM4/28/2009 11:20:46 AM