Engineering & Physical Data MVCU-2009
General Data - Cooling Only (R22)
MODEL
INDOOR UNIT MCM025D MCM030D
OUTDOOR UNIT MVCU025A MVCU030A
NOMINAL CAPACITY
Btu/h 24000 29500
W 7034 8646
NOMINAL TOTAL INPUT POWER W 2500 2934
NOMINAL RUNNING CURRENT A 12.8 5.2
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 380 - 415 / 3 / 50
EER W/W 2.81 2.95
REFRIGERANT TYPE R22 R22
REFRIGERANT CONTROL (EXPANSION DEVICE) OUTDOOR CAP. TUBE INDOOR CAP. TUBE
INDOOR UNIT
CONTROL
AIR DISCHARGE
AUTO LOUVER (UP & DOWN)
& MANUAL LOUVER (BOTTOM)
AUTO LOUVER (UP & DOWN)
& MANUAL LOUVER (BOTTOM)
OPERATION
WIRELESS OR WIRED
MICROCOMPUTER
REMOTE CONTROL
WIRELESS OR WIRED
MICROCOMPUTER
REMOTE CONTROL
AIR FLOW
HIGH l/s / CFM 297 / 630 326 / 690
MEDIUM l/s / CFM 274 / 580 297 / 630
LOW l/s / CFM 245 / 500 255 / 540
EXTERNAL STATIC PRESSURE (H/M/L) Pa / in.wg. --
SOUND PRESSURE LEVEL (H/M/L) dBA 54 / 53 / 50 51 / 50 / 48
UNIT DIMENSION
HEIGHT mm/in 214 / 8.4 249 / 9.8
WIDTH mm/in 1214 / 47.8 1214 / 47.8
DEPTH mm/in 670 / 26.3 670 / 26.3
PACKING DIMENSION
HEIGHT mm/in 301 / 11.9 345 / 13.6
WIDTH mm/in 1311 / 51.6 1361 / 53.5
DEPTH mm/in 760 / 29.9 760 / 29.9
UNIT WEIGHT kg/lb 43 / 95 45 / 99
CONDENSATE DRAIN SIZE
mm/in
19 / 3/4 19 / 3/4
OUTDOOR UNIT
AIR FLOW l/s / CFM 927 / 1965 1251 / 2650
SOUND PRESSURE LEVEL dBA 57 59
UNIT DIMENSION
HEIGHT mm/in 841 / 33.1 841 / 33.1
WIDTH mm/in 572 / 22.5 572 / 22.5
DEPTH mm/in 572 / 22.5 572 / 22.5
PACKING DIMENSION
HEIGHT
mm/in
950 / 37.4 950 / 37.4
WIDTH mm/in 660 / 26.0 660 / 26.0
DEPTH mm/in 660 / 26.0 660 / 26.0
UNIT WEIGHT kg/lb 64 / 141 70 / 154
PIPE CONNECTION
TYPE BRAZED VALVE BRAZED VALVE
SIZE
LIQUID mm/in 9.5 / 3/8 9.5 / 3/8
GAS mm/in 15.9 / 5/8 15.9 / 5/8
REFRIGERANT CHARGE kg/lb 2.0 / 4.3 2.2 / 4.9
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 0.8m
BELOW THE UNIT. (MCM025D)
SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m
BELOW THE UNIT. (MCM030D)