MVCU-2009 Application Information
Additional Charge
The refrigerant gas is charged in the outdoor unit and, if the piping length is 7.6m, additional charge of the
refrigerant after vacuuming is not necessary.
When the piping length is more than 7.6m, additional refrigerant charge (g) per additional 1m length as
tabulated:
Outdoor MVCU025A MVCU030A MVCU035/040/050/060A
L=10m 0.290 kg 0.650 kg 0.250 kg
L=15m 0.480 kg 0.900 kg 0.500 kg
L=20m - 1.150 kg 0.750 kg
L=25m - 1.400 kg 1.000 kg
L=30m - 1.650 kg 1.250 kg
L=35m - 1.900 kg 1.500 kg
Diagram shows typical charging method:
Overall Checking
Ensure the following, in particular:
1. The unit is mounted solidly and rigid in position.
2. Piping and connections are leak proof after charging.
3. Proper wiring has been done.
Drainage check – pour some water into drain pan.
Test run
1. Conduct a test run after water drainage test and gas leakage test.
2. Watch out for the following:
(a) Is the electric plug rmly inserted into the socket?
(b) Is there any abnormal sound from the unit?
(c) Is there any abnormal vibration with regard to the unit itself or piping?
(d) Is there smooth drainage of water?
Check that:
1. Outdoor fan is running, with warm air blowing off the outdoor unit (cooling cycle).
2. Indoor blower is running and discharge cool air (cooling cycle).
3. Suction (low side) pressure is as per recommendations.
4. The remote controller has incorporated a 3 minutes delay in the circuit. Thus, it requires about 3 minutes
before the outdoor unit can start up.
Standard Operating Condition
Temperature Ts °C / °F Th °C / °F
Minimum indoor temperature 19.0 / 66.2 15.0 / 59.0
Maximum indoor temperature 26.7 / 80.1 24.0 / 75.2
Minimum outdoor temperature 19.0 / 66.2 13.9 / 57.0
Maximum outdoor temperature 52.0 / 125.6 24.0 / 75.2
05_Application Information.indd 1805_Application Information.indd 18 4/28/2009 11:12:34 AM4/28/2009 11:12:34 AM