M5HDC-2010
Application Information
Piping Connection To The Units
• Align the center of the piping and sufciently tighten the are nut with ngers.
• Finally, tighten the are nut with torque wrench until the wrench clicks.
• When tightening the are nut with torque wrench, ensure the direction for tightening
follows the arrow on the wrench.
Pipe Size (mm/in) Torque (nm)
6.35 (1/4) 18
9.53 (3/8) 42
15.88 (5/8) 65
Vacuuming and Charging
• The precharged outdoor unit does not need any vacuuming or charging. However once
it is connected, theconnecting pipe line and the indoor need to be vacuumed before
releasing refrigerant from the outdoor unit.
1) Open the service port core cap.
2) Connect pressure gauge to the service port.
3) Connect the line to vacuum pump. Open the charging manifold valve and turn the
pump on. Vacuum to -0.1MPa (-760mmHg) or lower. (Evacuation time varies by the
pump but averagely in 1 hour).
LO HI
CHARGE SET
OUTDOOR UNIT
VACUUM PUMP
INDOOR UNIT
Flare Joint
Flare Valve
Diagram 1