12
M5HDC-2010
Wiring
Wiring Electrical Connections
• Wiring regulations on wire diameters differ from country to country. Please refer to your
LOCAL ELECTRICAL CODES for eld wiring rules. Be sure that installation comply with
such rules and regulations.
General Precautions
• Ensure that the rated voltage of the unit corresponds to the name plate before carrying
out proper wiring according to the wiring diagram.
• Provide a power outlet to be used exclusively for each unit. A power supply disconnect
and a circuit breaker for over-current protection should be provided in the exclusive line.
• The unit must be GROUNDED to prevent possible hazards due to insulation failures.
• All wiring must be rmly connected.
• All wiring must not touch the hot refrigerant piping, compressor or any moving parts of
fan motors.
Refrigerant Piping
Maximum Pipe Length And Maximum Number Of Bends
• When the pipe length becomes too long, both the capacity and reliability drop.
As the number of bends increases, system piping resistance to the refrigerant ow
increases, thus lowering the cooling capacity, and as the result the compressor may
become defective. Always choose the shortest path and follow the recommendation as
tabulated below:
Model
Data
Max. Length, L
15 m 15 m
Max. Elevation, H
8 m 8 m
Max. No. of Bends
10 10
M5HDC020AR M5HDC025AR
Piping Sizes (Flare Connection Type)
• Piping sizes are as follows:
Model M5HDC020AR M5HDC025AR
Liquid (mm/in) 6.35 (1/4) 9.52 (3/8)
Suction (mm/in) 15.88 (5/8) 15.88 (5/8)
Application Information