Mini Chiller: Trouble Shooting With Microprocessor
Error code display at the 7 segment LED:
Symptoms Possible Causes Remedial Action
1. PCB display "CO" * Compressor thermal relay tripped * Reset the thermal relay and carefully
monitor unit operation when it is restarted
* Terminal loose * Tighten terminal screws.
2. PCB display "PO" * Pump thermal relay tripped * Reset the thermal relay and carefully
monitor unit operation when it is
* Terminal loose * Tighten terminal screws.
3. PCB display "FL" * Flow switch connection loose * Tighten terminal screws.
* Water volume too low * Add water into the system
* Wrong direction of water flow * Interchange power input phase
4. PCB display "HP" * Discharge pressure too high * Reset the pressure switch and odserve
the unit operation when it is restarted
* Overcharge * Contact local dealer
* Coil dirty * Clean the coil with chemical detergent
* Condenser fan does not work * Contact local dealer
* Expansion valve stuck in open position * Replace it
5. PCB display "LP" * Suction pressure too low * Reset the pressure switch and observe
the unit operation when it is restarted
* Undercharge * Contact local dealer
* Gas leak * Contact local dealer
* Water flow rate too low * Adjust the flow rate
6. PCB display " E3" * Antifreeze protection activated * Check the temperature setting
* Water flow rate too low * Adjust the flow rate
* Bubble in the heat exchanger * increase the water volume
47 48
Roof Top Unit : Trouble Shooting Guide
Before you ask for repair service, check the following points
State of Machine Switch Box Cause Troubleshooting
(Field supply)
It does not run Switch (ON) Power failure Press the switch (ON) button after power
restoration
The power supply is turned OFF Turn the power supply ON
The fuse in the power supply is gone Replace fuse
The earth leakage breaker is gone Put in the earth leakage breaker.
The wiring phase of power supply is Modify the wiring phase of power supply
mistaken
Air flows out Switch (ON) Improper temperature adjustment After checking the set temperature and inlet
but it does not temperature adjust thermostat (23WA)
cool enough The filter is filled with dust and dirt. Clean up the filter
There are some obstacles at the air inlet Remove the obstacle
and outlet of the units
Windows and doors are open Close the windows and doors
Cool air does not Switch (ON) The restart-preventing circuit is in Wait for a while
come out operation for 3 minutes (To protect the compressor, a 3-minute restart-
preventing circuit is built into the unit.
Therefore, there are occasions sometimes when
the compressor does not start running
immediately. There are cases when it does not
run for as long as 3 minutes.)
Fan runs but compressor does not The set temperature of thermostat is For temperature control, decrease the set
run excessively high for cooling temperature at cooling.
The room temperature is excessively low Can not be operated as it is out of temperature
for cooling control range.
Compressor run but stops Air outlet and inlet are blocked Remove blocking matter
immediately
Water or steam is discharged from At cooling, water which places to cooling It is not a breakdown.
the unit. piping and pipng connection part drops Please use it as it is