7. General Troubleshooting Guide
By means of pressure readings
PRESSURE PROBABLE CAUSE
Data
Circuit
HIGH SIDE 1. Overcharged with refrigerant.
LOW SIDE 2. Non-condensable gases in refrigerant circuit
(eg.oil)
3. Obstructed air-intake / discharge.
4. Short circuiting of hot air at condensing unit.
HIGH SIDE 1. Poor compression / no compression
LOW SIDE ( compressor defective )
2. Check valve stick in open position.
3. Reversing valve leaking (for heatpump only).
HIGH SIDE 1. Undercharged with refrigerant.
LOW SIDE 2. Refrigerant leakage.
3. Air filter clogged / dirty (indoor unit)
4. Indoor fan locked (cooling)
5. Defective defrost control, outdoor coil freezed
up (heating)
6. Outdoor fan locked (heating)
HIGH SIDE 1. Outdoor fan blocked (cooling)
LOW SIDE 2. Outdoor coil dirty (cooling)
3. Indoor fan lock (heating)
4. Indoor filter clogged dirty (heating)
HIGH SIDE 1. Air intake temperature of indoor unit too high.
LOW SIDE
TOO LOW
TOO HIGH
NORMAL
A LITTLE
LOW
A LITTLE
HIGH
O. AIR COOLED MINI CHILLER
Model Board
AC40/50/58A/AR SZMC01
AC75/100/125B/BR
System Failure Mode
No Description Error Code Compressor Condenser 4WV Water LED
Display Fan Pump
1 Compressor overload CO X X X O B
2 Condenser fan overload CO X X X O B
3 Water pump overload PO X X X X B
4 Flow switch FL X X X X B
5 High pressure cut-off HP X X X O B
6 Low pressure cut-off LP X X X O B
X = Stop; O = Run; B = Blink
Error Code
Display Possible Causes
“CO” Compressor thermal relay trip
Terminal loose
“PO” Pump thermal relay trip
Terminal loose
“FL” Flow switch connection fault
Water flow wrong connection
Flow switch fault
“HP” Discharge pressure high
Overcharged
Coil dirty
Condenser fan fault
“LP” Suction pressure low
Undercharged/leak
Water flow rate too low
“E3” Antifreeze protection activated
Water flow rate too low
Model Board Handset
AC80/100/120/150C/CR MCH03 Chiller Panel
*Error is directly displayed on Chiller Panel’s LCD display panel.