McQuay MDS300B Installationsanleitung Seite 74

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 120
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 73
-74-
Design & installation Guide For McQuay MDS Multi System
4.1.3 High static pressure duct unit
In order to keep the unit runs in a good condition, the air inlet port should be at least 3m.
Soft connecting joint should be used to reduce the sound level and the vibration.
Condensated water pipe should have a slope with no less than 0.5%~1%, and it must be
insulated.
Condensate water pipe should have a trap. The trap should be PVC pipe, and the diameter of the
trap should be more than or equals to that of the condensated water pipe.
If the unit installed in the ceiling, the condensated water pipe must connected to drainage pipe;
and if it installed on the floor, then the condensated water can drain to the drainage pipe directly.
The installation of MDB unit, electric heater, hot water heating and ME energy saver are as
follows:
Seitenansicht 73
1 2 ... 69 70 71 72 73 74 75 76 77 78 79 ... 119 120

Kommentare zu diesen Handbüchern

Keine Kommentare