26
(3) REFRIGERANT PIPING
MAXIMUM PIPING LENGTH AND MAXIMUM NUMBER OF BENDS
When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends
increases, system piping resistance to the refrigerant flow increases, thus lowering the cooling capacity, and
as the result the compressor may become defective. Always choose the shortest path and follow the recom-
mendation as tabulated below:
Piping Sizes (Flare Connection Type)
Piping sizes are as follows:
Piping Connection to the Units
• Align the center of the piping and tighten the flare nut sufficiently with fingers.
• Finally tighten the flare nut with torque wrench unit the wrench clicks.
• When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on
the wrench.
Pipe Size (mm/in) Torque (Nm)
6.35 (1/4) 18
9.52 (3/8) 42
12.70 (1/2) 55
15.88 (5/8) 65
19.05 (3/4) 78
Indoor 015E/ER 020E/ER 025E/ER
Outdoor 015C/CR 018 / 020C/CR 025C/CR 028C/CR 030 / 035C/CR
12 15 15 15 45
588825
10 10 10 10 10
Maximum No. of Bends
Model
028E/ER
Maximum Length, m
Maximum Elevation, m
Model
MLC 015C/CR MLC 018/020C/CR MLC 025C/CR MLC 028C/CR MLC 030C/CR
Liquid (mm/in)
6.35 /
1
/
4
6.35 /
1
/
4
9.52 /
3
/
8
9.52 /
3
/
8
9.52 /
3
/
8
Suction (mm/in)
12.70 /
1
/
2
15.88 /
5
/
8
15.88 /
5
/
8
15.88 /
5
/
8
15.88 /
5
/
8
Model
M5LC 015C/CR M5LC 020C/CR M5LC 025C/CR M5LC 028C/CR M5LC 035C/CR
Liquid (mm/in)
6.35 /
1
/
4
6.35 /
1
/
4
6.35 /
1
/
4
9.52 /
3
/
8
9.52 /
3
/
8
Suction (mm/in)
12.70 /
1
/
2
12.70 /
1
/
2
15.88 /
5
/
8
15.88 /
5
/
8
15.88 /
5
/
8
R22
R410A