M5CKWS040AR/M5WSS040AR
Cooling Only/ Cooling Mode (Heatpump)
Water Flow Rate = 1.26 m
3
/hr
Water Flow Rate = 2.10 m
3
/hr
Water Flow Rate = 2.94 m
3
/hr
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 25 30 35 40 45
TC 11.18 10.70 10.35 10.01 9.46 8.90 8.35
SC 10.94 10.49 10.18 9.86 9.35 8.85 8.34
TC
11.60 11.08 10.71 10.34 9.73 9.12 8.50
SC 10.02 9.69 9.45 9.21 8.84 8.46 8.09
TC
12.16 11.59 11.19 10.79 10.09 9.40 8.70
SC 8.81 8.60 8.46 8.09 8.13 7.94 7.76
TC 12.29 11.79 11.43 11.07 10.42 9.77 9.11
SC
8.07 7.89 7.76 7.63 7.45 7.27 7.10
TC 12.70 12.39 12.16 11.93 11.40 10.87 10.34
SC
5.96 5.84 5.75 5.67 5.51 5.36 5.22
TC 12.84 12.58 12.40 12.22 11.73 11.24 10.75
SC
5.27 5.18 5.11 5.05 4.90 4.75 4.61
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 25 30 35 40 45
TC
11.69 11.18 10.82 10.47 9.89 9.31 8.73
SC 11.44 10.97 10.64 10.31 9.78 9.25 8.72
TC 12.13 11.59 11.20 10.81 10.17 9.53 8.89
SC
10.48 10.13 9.88 9.64 9.24 8.85 8.46
TC 12.71 12.12 11.70 11.28 10.55 9.83 9.10
SC
9.21 9.00 8.85 8.46 8.50 8.30 8.11
TC 12.86 12.33 11.95 11.58 10.90 10.21 9.53
SC 8.44 8.25 8.11 7.98 7.79 7.61 7.43
TC
13.28 12.95 12.71 12.48 11.92 11.37 10.81
SC 6.23 6.10 6.01 5.93 5.77 5.61 5.45
TC
13.43 13.16 12.97 12.77 12.26 11.75 11.24
SC 5.51 5.42 5.35 5.28 5.12 4.97 4.82
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 25 30 35 40 45
TC 11.94 11.43 11.06 10.69 10.10 9.51 8.92
SC 11.68 11.21 10.87 10.53 9.99 9.45 8.91
TC
12.39 11.84 11.44 11.05 10.39 9.74 9.08
SC 10.71 10.35 10.09 9.84 9.44 9.04 8.65
TC
12.99 12.39 11.95 11.52 10.78 10.04 9.30
SC 9.41 9.19 9.04 8.64 8.69 8.48 8.29
TC 13.13 12.60 12.21 11.83 11.13 10.43 9.73
SC
8.63 8.43 8.29 8.15 7.96 7.77 7.59
TC 13.57 13.23 12.99 12.74 12.18 11.61 11.05
SC
6.36 6.24 6.14 6.05 5.89 5.73 5.57
TC 13.72 13.44 13.25 13.05 12.53 12.00 11.48
SC 5.63 5.53 5.46 5.39 5.23 5.08 4.92
23
24
15.5
17
19
20
Entering Water Temperature, (°C)
27.0
15.5
17
19
20
23
24
15.5
17
Entering Water Temperature, (°C)
27.0
Entering Water Temperature, (°C)
27.0
19
20
23
24
Note:
1. DB = Dry Bulb, WB = Wet Bulb, TC = Total Capacity, SC = Sensible Capacity
2. All datas above are generated at delta T = Leaving Water Temperature - Entering Water Temperature = 5
°C
122