McQuay Service Guide Book
82
Fuse for
operation
circuit
Evaporator fan
contactor
Evaporator fan
contactor
Evaporator fan
contactor
Over current
relay for
evaporator fan
By means of diagnostic flows chart:
Generally, there are two kinds of problems, i.e. starting failure and insufficient cooling/ heating.
“Starting failure” is caused by electrical defect while improper application or defects in refrigerant
circuit causes “insufficient cooling/ heating”.
i) Diagnosis of Electric circuit
: Faulty : Check : Cause : Remedy
NO cooling/ heating (Unit fail to start)
Unit Power
supply
Evaporator
fan motor
2 1
No voltage or low voltage
Wrong phase/ missing
phase
Components shorted
Components loose
High or low voltage
Wron
g / missing phase
Coil burned
Contact faulty
Faulty fan motor
Defective operation
Defective operation
Wrong/ missing phase
Get the right voltage
Stop
Repair the power line
Repair or replace the
components
Tighten the connections
Get the right v
oltage
Check the power supply
to the motor: repair
when necessary
Change the contactor
Repair the contact
Repair or change the
motor
Repair or change the
switch
Get the right voltage
Check the power supply
to the motor: repair
when necessary